ASS RCD does not trip
ID: 160367
Description: If you touch a live part and get an electric...
Steps:
- the circuit breaker works with the IC RV4145, which requires 26V, but there are 230V on the line, the excess is 'burned off' in a large resistor
- directly next to the resistor sits (stands) a small electrolytic capacitor, a design flaw, because electrolytic capacitors do not like heat ..... after a few years they are defective
- and the dangerous thing here is, you don't notice anything ..... current still flows .......
- Only by pressing the 'Test' button do you notice the defect!
- Desolder the defective electrolytic capacitor.
- To make the new electrolytic capacitor last longer, install it on the underside... it is not as hot there.
- Observe the polarity, see the photo for +.
- When testing without switching off, the small test resistance can burn out and must then also be replaced; 6.8 kΩ for 30mA RCD (18 kΩ in the photo).
- so, attention, such an RCD is not 'fail-safe'
- therefore regularly press the 'Test' button !